MoniTach Substation Monitoring System: IEC 61850 Remote Monitoring for 220kV and 440kV Switchyards

MoniTach — The Tachyons Yard Intelligence — is the substation remote monitoring system from Tachyons Energy Private Limited, Kerala, India, for 220kV and 440kV switchyards and their control and distribution panels. It continuously monitors circuit breakers, SF6 gas density, power transformers (OTI, WTI, Buchholz, OLTC), isolators, trip circuits, busbar temperatures and feeder telemetry, and raises early-warning alarms on a SCADA / web dashboard with SMS and voice escalation. It connects over IEC 61850, Modbus TCP/RTU and hardwired I/O, and it supervises and reports — protection tripping stays with the existing relays.

  • 220kV
  • 440kV
  • IEC 61850 · MMS / GOOSE
  • Modbus TCP / RTU
  • Optical fibre

What MoniTach monitors in the switchyard and control room

MoniTach watches the equipment whose slow deterioration causes most substation failures, and alarms on the trend before the equipment’s own alarm or trip stage is reached. In the yard it covers circuit breakers, SF6 compartments, power transformers and isolators; in the control room it covers relay and trip circuit health, thermal hot spots and feeder telemetry. Each signal is compared against its commissioning baseline, so a breaker that charges its spring more slowly or a joint running hotter than its neighbours is flagged early.

  • Circuit breakers: position, spring-charging motor current and time, trip coil health, contact wear
  • SF6 compartments: continuous pressure, temperature-compensated density, micro-leak trend
  • Power transformers: OTI, WTI, Buchholz alarm and trip contacts, OLTC tap position, breather health
  • Isolators and earth switches: position, interlock verification, drive motor current and operating time
  • Relay and trip circuits: DC trip supply, trip circuit continuity, auxiliary and lockout (86) relay status
  • Thermal and busbar: termination, joint and contact temperatures against ambient
  • Feeders: three-phase voltage and current, power factor, harmonics and transient waveforms

SF6 gas density monitoring, and why density matters

SF6 (sulphur hexafluoride) is the gas that insulates and quenches the arc inside many high-voltage circuit breakers and gas-insulated switchgear. What protects the breaker is the gas density — the amount of gas in the compartment — because pressure alone rises and falls with temperature; a breaker is alarmed and then blocked from operating when density falls too low. MoniTach uses a temperature-compensated density transmitter mounted alongside the existing density monitor, so a slow micro-leak shows up as a steady decline weeks before the breaker’s own alarm stage, and SF6 losses to the atmosphere are kept down.

IEC 61850, Modbus and hardwired I/O

IEC 61850 is the international standard for communication in substation automation: it defines how protection relays and other intelligent electronic devices (IEDs) describe their data and exchange it over the station Ethernet bus. In modern substations MoniTach joins that bus as an IEC 61850 client, reading IEDs over MMS and subscribing to GOOSE messages, so it does not duplicate sensors the protection and control system already has. Meters, PLCs and sensors are polled over Modbus TCP/RTU, and older electromechanical equipment is covered with potential-free contacts and 4–20 mA signals, so a mixed-age yard appears on one dashboard.

  • IEC 61850 MMS client for relays, bay control units and other IEDs
  • GOOSE subscription for fast breaker and interlock status changes
  • Buffered and unbuffered reports so events during a link outage are not lost
  • Engineering from SCL files (ICD / CID / SCD) so signal names match scheme drawings
  • Modbus TCP / RTU over Ethernet or RS-485 for meters, PLCs and transmitters
  • Hardwired potential-free contacts and 4–20 mA signals for legacy equipment
  • Time-stamping against the station clock (SNTP or PTP)

Optical-fibre yard network and supervision-only design

Signals from the yard data concentrators reach the control room over optical fibre, which carries no current and so provides galvanic isolation from earth potential rise and induced surges in the switchyard. An edge gateway normalises IEC 61850, Modbus and hardwired data and feeds the SCADA / web dashboard and SMS and voice escalation. MoniTach reads and reports; protection tripping and interlocking remain with the substation’s protection and control scheme, and it is designed to work on redundant PRP / HSR station-bus networks where the substation uses them.

HOW THE WORK RUNS

How we deliver monitach monitoring

  1. 01

    Site survey and signal list

    Survey of the yard and panels, review of single-line and scheme drawings, existing IEDs and SCL files, and agreement of the signal list.

  2. 02

    Architecture and engineering

    Choice of IEC 61850, Modbus or hardwired connection per equipment, sensor selection, fibre routes, gateway and dashboard configuration.

  3. 03

    Installation

    Sensors and transmitters mounted alongside existing devices, yard data concentrators, optical-fibre network and edge gateway, with work on live circuits planned into shutdown windows.

  4. 04

    Point-to-point testing

    Every signal checked from the field device to the dashboard against the signal list, including alarm thresholds and escalation.

  5. 05

    Baseline and commissioning

    Commissioning baselines recorded for each monitored item, alarm stages set, and the system put into service with operator training.

QUESTIONS & ANSWERS

MoniTach Monitoring: common questions

Straight answers to what clients ask us most before a project starts.

What is the difference between Modbus and IEC 61850 in a substation?

Modbus is a simple master–slave protocol that reads numbered registers from meters, PLCs and sensors, so the meaning of each register must be mapped by hand. IEC 61850 is a substation-specific standard in which each IED describes its own data model, supports event reporting and fast GOOSE messages, and is engineered from standard SCL configuration files. MoniTach uses IEC 61850 where IEDs are networked and Modbus for meters, PLCs and transmitters.

Can a monitoring system be retrofitted to an old substation?

Yes. Legacy electromechanical equipment is monitored through potential-free auxiliary contacts and 4–20 mA signals wired to a yard data concentrator, and add-on sensors such as SF6 density transmitters are mounted alongside the existing devices rather than replacing them. Where connections into live circuits are needed, the work is planned into shutdown windows. What can be monitored depends on the signals the existing equipment can provide.

Does MoniTach replace protection relays or the substation SCADA?

No. MoniTach supervises and reports on equipment condition; protection tripping and interlocking stay with the substation’s protection relays and control scheme. It reads data from IEDs and sensors and presents early warnings on its own dashboard, and its northbound interfaces to other systems are fixed per project.

Why monitor SF6 density instead of pressure?

The insulating and arc-quenching strength of SF6 depends on its density, while its pressure changes with temperature through the day even when no gas is lost. A temperature-compensated density reading removes that variation, so a genuine leak shows up as a steady downward trend. That allows a planned leak repair and top-up before the breaker reaches its low-density alarm or operation-block stage.

Which transformer parameters does the system monitor?

MoniTach monitors oil temperature (OTI), winding temperature (WTI), Buchholz relay alarm and trip contacts, OLTC tap position and breather condition. Temperatures are taken from the OTI / WTI repeater outputs or parallel PT100 elements, and relay states from potential-free contacts. The transformer’s own Buchholz and temperature trips remain wired to its protection.

How are alarms delivered to the maintenance team?

Alarms appear on the SCADA / web dashboard and are escalated by SMS and voice call to the assigned staff. Events are time-stamped against the station clock so their sequence lines up with relay records. Alarm thresholds and escalation lists are set per site during commissioning.